Baldor Automobile Parts DTM8000 User Manual

DTM8000  
Digital Tachometer  
Installation and Operating Manual  
LT49 (A-5-3196A)  
MN1327  
 
Quick Jump  
What models and recommended accessories are  
available?  
See page 3ꢀ  
Looking for detailed specifications?  
See page 3ꢀ  
Want to get started fast?  
See basic electrical hook-up details on page 5ꢀ  
See mechanical installation details on page 4ꢀ  
See some sample applications starting on page 15ꢀ  
Need Help?  
See troubleshooting on page 19ꢀ  
LIMITED WARRANTY  
Foraperiodofone(1)yearfromthedateoforiginalpurchase,BALDORwillrepairorreplacewithoutchargecontrols  
and accessories which our examination proves to be defective in material or workmanship$ This warranty is valid if  
theunithasnotbeentamperedwithbyunauthorizedpersons,misused,abused,orimproperlyinstalledandhasbeen  
used in accordance with the instructions and/or ratings supplied$ This warranty is in lieu of any other warranty or  
guaranteeexpressedorimplied$BALDORshallnotbeheldresponsibleforanyexpense(includinginstallationand  
removal),inconvenience,orconsequentialdamage,includinginjurytoanypersonorpropertycausedbyitemsofour  
manufacture or sale$ (Some states do not allow exclusion or limitation of incidental or consequential damages, so  
theaboveexclusionmaynotapply$)Inanyevent,BALDOR’stotalliability,underallcircumstances,shallnotexceed  
the full purchase price of the control$ Claims for purchase price refunds, repairs, or replacements must be referred  
to BALDOR with all pertinent data as to the defect, the date purchased, the task performed by the control, and the  
problem encountered$ No liability is assumed for expendable items such as fuses$  
GoodsmaybereturnedonlywithwrittennotificationincludingaBALDORReturnAuthorizationNumberandanyreturn  
shipments must be prepaid$  
WARNING  
Improper installation or operation of this control may cause injury to personnel or control failureꢀ The control must be  
installedinaccordancewithlocal,state,andnationalsafetycodesMakecertainthatthepowersupplyisdisconnected  
before attempting to service or remove any components!!! If the power disconnect point is out of sight, lock it in  
disconnected position and tag to prevent unexpected application of powerꢀ Only a qualified electrician or service  
personnel should perform any electrical troubleshooting or maintenanceꢀ At no time should circuit continuity be  
checked by shorting terminals with a screwdriver or other metal deviceꢀ  
 
Table of Contents  
Introduction ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ2  
General Featuresꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ2  
Models & Options ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ3  
Model Tableꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ3  
Recommended Accessories ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ3  
Specificationsꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ3  
Electricalꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ3  
Mechanical ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ3  
Environmental ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ3  
Mechanical Installationꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ4  
Exploded Panel View ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ4  
Cut-out and Mounting Dimensions ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ4  
Electrical Installation & Diagrams ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ5  
P1 Terminal Block Wiring Diagram ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ5  
P1 Terminal Block Descriptions ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ5  
Basic Operating Instructions ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ6  
Rate, Time, and Counter Modes Explained ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ6  
Visual Reference ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ6  
How to Change a Parameter's Value (The Short Story) ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ6  
Operating the User Interface (The Long Story)ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ6  
Detailed Configuration Instructions ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ7  
Factory Set Configurationꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ7  
Resetting the Unit to Factory Settings ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ7  
JP1 (Program Enable Jumper)ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ7  
Software Parameters ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ8  
Parameter Descriptions ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ10  
Application Examples ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ15  
Pump Flow Monitor with Audible and Visual Alarm ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ15  
Conveyor Oven Time Monitor with Over-Heating Alarm ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ16  
Take-up / Pay-out Reel Material Measurement with Alarmꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ17  
Bi-directional Incremental Position Display ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ18  
Troubleshooting ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ19  
Download from Www.Somanuals.com. 1All Manuals Search And Download.  
Introduction  
The DTM8000 Digital Meter is a powerful, microprocessor-based unit capable of being configured for  
anumberoftoday’sdemandingmeasurementneedsItcanbequicklyconfiguredtooperateasadigital  
rate meter, timer, or feature-filled process counterꢀ It also offers up to two alarm outputs which can be  
adjustedforanumberoftriggerconditionsꢀ Itsdurable1/8DINaluminumhousingcanbeeasilymounted  
in a panel or control cabinetꢀ Flexibility makes the DTM8000 ideal for applications such as:  
Pay-out and Take-up Limit Monitors  
Conveyor Oven “Tunnel-Time” Monitors  
Rotating Machinery Tachometers  
MaterialMeasurementMeters  
General Features  
- Microprocessor-based design combines responsiveness and accuracy in one package  
- Selectable display update rate  
- Capable of measuring shaft speeds lower than 1 RPM @ 1 pulse per revolution  
- Large 4 digit, ½” LED display  
- Field programmable via front-panel keypad  
- Lexan membrane and gasket (which are included) meet NEMA 4X standards when used with NEMA  
4X enclosures  
- Internal program-enable jumper selectively prevents tampering with unit’s configuration  
- Universal power supply accepts line voltages inputs from 85-265VAC @ 50-60Hz without switches  
or jumpersꢀ The unit automatically adjusts as neededꢀ  
- Non-volatile memory stores adjustable parameters even when power has been removed  
- Compatible with a variety of signal input types including: Hall-Effect Pickups, Photoelectric, TTL, etcꢀ  
Note: Open collector devices must be capable of sinking 3mAꢀ  
- Wide operating ambient temperature range of -10C to 45C (14F to 113F)  
- Self-contained power supply for external sensor, limited to 5V @ 50mA  
- Up to 2 programmable alarm outputs with Form C contacts rated to 250VAC @ 5A  
- Multiple auto-ranging features allow the user to view display values from 0ꢀ001 to 99,990 in any user-  
defined unitꢀ (GPH, MPH, RPM, etcꢀ)  
- Multiple operating modes including:  
Rate Mode – Displays in rate unit such as RPM, Gallons per Second, etcꢀ  
Time Mode – Displays in time unit such as HH:MM, MM:SS, SS:TT, or other unit  
Counter Modes – Displays resettable and reloadable counter value which can optionally  
increment or decrement for each input pulseꢀ Quadrature inputs can automatically  
be translated to up/down counts for bidirectional applications  
Download from Www.Somanuals.2com. All Manuals Search And Download.  
Models & Options  
Model Table  
Quadrature  
Encoder  
Compatible?  
Model  
DTM8000-6  
Input Voltage  
Alarm  
Outputs  
Measures  
Rate?  
Measures  
Time?  
Up  
Counter?  
Down  
Counter?  
85-265VAC  
1
Yes  
Yes  
Yes  
Yes  
Yes  
RecommendedAccessories  
Pulses per  
Revolution  
RPM Range When Used With  
DTM8000  
Model  
Description  
HPU10  
RK60-56  
RK60-145  
Hall-Effect Pickup, Single Channel  
Hall-Effect Pickup, Single Channel  
Hall-Effect Pickup, Single Channel  
10  
60  
60  
0.1 – 10,000 RPM  
0.02 – 1,600 RPM  
0.02 – 1,600 RPM  
Specifications  
Electrical  
Line Input Voltage----------------------------------------------------------------------------------Any Voltage from 85-265 VAC  
Line Input Frequency--------------------------------------------------------------------------------- Any Freq. from 48-62 Hertz  
Signal Input Frequency Range----------------------------------------------------------------- 0 – 100,000 Pulses per Minute  
(Higher frequencies are possible when using internal frequency divisor)  
Display Range--------------------------------------------------------------------------------------------------------- 0.001 – 99,990  
Units of Operation----------------------------------------------------------------------------------User Programmable, any Unit  
Sensor / Pickup Power Supply-----------------------------------------------------------------------------------------5V @ 50mA  
Isolated Alarm Relay Output Ratings ------------------------------------------------------------------------------240VAC @ 5A  
Mechanical  
Display Type ---------------------------------------------------------------------------------------------LED, Red, 4 Digit, ½” Height  
Housing Type (with supplied gasket in NEMA 4X panel)-------------------------------------------------------------- NEMA 4X  
Connector Style -----------------------------------------------------------------------------------12-position 5mm European Style  
Terminal Block Torque Setting ------------------------------------------------------------------------------ 4.4 in. lb. Max or .5Nm  
Faceplate Material--------------------------------------------------------------------------Polycarbonate with GE Lexan Overlay  
Housing Material ----------------------------------------------------------------------------------------------------------------- Aluminum  
Length (Required Panel Depth) ----------------------------------------------------------------------------------- 4.625", 117.48mm  
Faceplate Width ------------------------------------------------------------------------------------------------------ 4.539", 115.29mm  
Weight ------------------------------------------------------------------------------------------------------ .8425 lb, 13.48 oz, 382.14g  
Environmental  
Operating Temperature Range------------------------------------------------------------------------10C to 45C (15F to 115F)  
Operating Humidity Range--------------------------------------------------------------------------------- 95%, non-condensing  
Download from Www.Somanuals.com. 3All Manuals Search And Download.  
Mechanical Installation  
Exploded Panel View  
PANEL MOUNTING GASKET  
(WITH THE ADHESIVE SIDE OF  
GASKET FACING THE CUSTOMER  
MOUNTING PANEL)  
CUSTOMER  
MOUNTING PANEL  
(HOLE CUT-OUT FOR CONTROL  
HOUSING APPROXIMATELY  
3.622" WIDE BY 1.770" HIGH)  
DTM8000 SERIES  
TACHOMETER  
SUPPLIED WITH EACH CONTROL:  
1) GASKET  
2) (2) 6-32 X 3/4 PANHEAD BLACK OXIDE STAINLESS SCREWS  
3) (2) #6 NUT WITH LOCKWASHER  
Cut-out and Mounting Dimensions  
4.000"  
5.000"  
ENTER  
2.289"  
1.656"  
TACHOMETER  
4.000"  
4.625"  
3.622  
"
DTM8000-6  
HOUSING DEPTH  
4.625"  
0.885"  
1.770"  
.140 x 2  
"
PANEL CUT-OUT  
Download from Www.Somanuals.4com. All Manuals Search And Download.  
Electrical Installation & Diagrams  
P1 Terminal Block Wiring Diagram  
NC2  
C2  
Alarm Output 2 - Normally Closed  
Alarm Output 2 - Common  
P1-1  
P1-2  
P1-3  
P1-4  
P1-5  
P1-6  
P1-7  
P1-8  
Form C Relay Output (Programmable)  
}
NO2  
NC1  
C1  
Alarm Output 2 - Normally Open  
Alarm Output 1 - Normally Closed  
Alarm Output 1 - Common  
Alarm Output 1 - Normally Open  
AC NEUTRAL  
Form C  
Relay Output  
DTM8000-6  
HOOK-UP  
}
NO1  
N
(Programmable)  
AC LINE INPUT  
L
2 Amp  
85-265VAC  
AC LINE  
}
AC LINE INPUT  
PICK-UP  
MOUNTED  
COM  
+5V  
S1  
black  
red  
COMMON  
+5VDC  
P1-9  
P1-10  
P1-11  
P1-12  
white  
SIGNAL 1  
SIGNAL 2  
S2  
*
* Used for various functions, including quadrature counter mode.  
P1 Terminal Block Descriptions  
P1-1 (2NC) – This is the normally-closed contact of the second user assignable relay outputꢀ  
P1-2 (2C) – This is the common contact of the second user assignable relayꢀ  
P1-3 (2NO) – This is the normally-open contact of the second user assignable relay outputꢀ  
P1-4 (1NC) – This is the normally-closed contact of the first user assignable relay outputꢀ  
P1-5 (1C) – This is the common contact of the first user assignable relayꢀ  
P1-6 (1NO) – This is the normally-open contact of the first user assignable relay outputꢀ  
P1-7 (AC / N) – For single phase AC lines connect the Neutral side of your AC line to this terminalꢀ For  
systems with two hot AC lines, connect either of the Hot AC lines to this terminalꢀ  
P1-8 (AC / L) – For single phase AC lines connect the Hot side of your AC line to this terminalꢀ For  
systems with two hot AC lines, connect either of the Hot AC lines to this terminalꢀ  
P1-9 (COM) – This is the common point for the control logicꢀ The speed sensor common lead as well  
as any other source needing to reference the control common will be connected to this terminalꢀ  
P1-10 (+5V) – This is a self-contained +5VDC power supply capable of up to 50mAꢀ The speed sensor  
supply lead can be connected to this terminal for its power sourceꢀ  
P1-11 (S1) – This is the Signal input terminal for single channel operation or channel 1 of dual channel  
operationꢀ The signal lead of your speed or counter sensor will be connected hereꢀ  
P1-12 (S2) – This is the Signal input terminal for channel 2 during dual channel operationꢀ The second  
signal lead of the speed or position sensor should be connected hereꢀ This terminal is also used  
as a reset input or function change input for various operations of the controlꢀ In counter modes,  
this input may also be used as a counter reset or enable gateꢀ  
Download from Www.Somanuals.com. 5All Manuals Search And Download.  
Basic Operating Instructions  
Rate, Time, and Counter Modes Explained  
In Rate Mode, the DTM8000 measures the input frequency, converts it to the user-defined units, and  
displays the rate in the display window of the user interfaceꢀ Most applications utilize rate mode and  
display in units such as gallons-per-minute, feet-per-second, and RPMꢀ  
In Time Mode, the DMT8000 measures the input frequency, converts it to the user-defined time units,  
and displays the time in the display windowꢀ This mode is most-commonly used in time-sensitive  
processes such as conveyor ovens and plating applicationsꢀ  
In Counter Modes, the DTM8000 counts each incoming pulse, scales it per the user-defined ratios, and  
displays the count in the display windowꢀ Typical counting applications include linear material  
measurement, cycle counters, and liquid volume measurementꢀ  
VisualReference  
ENTER (Select) Button  
ENTER  
TACHOMETER  
Up & Down Buttons  
Display Window  
How to Change a Parameter's Value (The Short Story)  
1ꢀ Hold down the Enter button until Parameter-Selection Mode is entered  
2ꢀ Using the Up and Down buttons, select the desired parameter number to view or edit  
3ꢀ Press the Enter button to change the value of the parameter  
4ꢀ Using the Up and Down buttons, change the parameter's value as desired  
5ꢀ Press the Enter button to permanently save the changes (Return to Parameter-Selection Mode)  
6ꢀ Select parameter zero and press the Enter button to return to Running Mode  
Operating the User Interface (The Long Story)  
The LED display has three basic operating modes: Running Mode, Parameter-Selection Mode, and  
Value Modeꢀ Each of the three modes have specific visual indicators that allow the user to immediately  
determine the current state or mode of the user interfaceꢀ Parameter-Selection Mode and Value  
Mode can only be entered if the Program Enable jumper is in the “On” positionꢀ  
Download from Www.Somanuals.6com. All Manuals Search And Download.  
Running Mode is the default display of the unit when power is appliedꢀ In Running Mode, the display  
shows the measured value in the appropriate user-defined format of rate, time, or countꢀ As the input  
signal changes, the display is continuously updated to show the latest measurementꢀ In this display  
mode, the Up and Down buttons serve no function other that to reset or silence alarms if configured  
accordinglyꢀ Example displays for rate, time, and count operating modes are 13ꢀ60, 45:30, and 9301ꢀ  
Parameter-Selection Mode can be entered by simply pressing and holding the Enter button down for  
three secondsꢀ Once in Parameter-Selection Mode, the far left of the display will be a ‘P’ꢀ The right side  
of the display will indicate the currently selected parameter number for editing purposesꢀ Pressing the  
Up or Down button will increase or decrease the selected parameter number on the displayꢀ Although  
the parameter numbers are in numerical order, some numbers are skippedꢀ These numbers represent  
reserved parameters that are not displayedꢀ Once the desired parameter number is displayed, a press  
of the Enter button will change the display to the Value Modeꢀ When in Parameter-Selection Mode,  
pressing the Enter button with parameter 0 selected will cause the unit to return to Running  
Modeꢀ Example displays for Parameter-Selection Mode are P 1, P 11, and P 54ꢀ  
Value Mode is used to modify the value of the selected parameterꢀ When in Value Mode, the two dots  
which form the colon, between digits two and three, will alternately flash (one, then the other) to inform  
the user that a parameter’s value is being editedꢀ Pressing the Up or Down button increases or  
decreasestheselectedparameter’svalueꢀ Valuechangestakeeffectimmediatelyꢀ Forexample,when  
scrolling through the alarm output conditions, the relay will activate as the always-active selection is  
passedꢀ Once the desired value is showing in the display window, pressing the Enter button again will  
return to Parameter-Selection Modeꢀ The new value is not saved in permanent memory until the Enter  
button is pressedꢀ Removing power from the unit while in Value Mode may result in the specified new  
value being lostꢀ  
Detailed Configuration Instructions  
Factory Set Configuration  
When shipped from the factory, the following basic settings are in place:  
Rate Mode Operation in RPM  
S1 Signal Input Pulses-per-Revolution: 10  
Decimal Point Display: Off  
Auto-Ranging: Disabled  
Alarm Output(s): Disabled  
Resetting the Unit to Factory Settings  
The factory settings can be easily restored using either of two methodsꢀ Both methods require the  
Program Enable jumper to be in the “On” positionꢀ The first is to apply power to the unit with both the  
Enter and Down buttons pressed for 3 secondsꢀ The second is to change the value of parameter 95  
to 5ꢀ  
JP1 (Program Enable Jumper)  
The JP1 jumper is located under the dust cover on the back end of the upper boardꢀ When the jumper  
is set to the "Off" position, all programming features are locked out to the front panel userꢀ When the  
jumper is in the "On" position, the programming parameters are open to changeꢀ JP1 is shipped from  
the factory set in the "On" positionꢀ  
Download from Www.Somanuals.com. 7All Manuals Search And Download.  
Software Parameters  
Value Range  
(units)  
Factory  
Settings  
n/a  
User  
Parameter  
Description  
Settings  
0
Selecting this item exits to Running Mode  
n/a  
Read-Only Parameters  
Model Number  
1
2
3
4
5
n/a  
80  
n/a  
n/a  
n/a  
n/a  
Software Build  
1 – 9999  
1 – 9999  
n/a  
Hardware Version  
Serial Number – Major (reserved)  
Serial Number – Minor (reserved)  
n/a  
General Setup  
10  
Operating Mode  
1 – Rate Mode  
1
2 – Time Mode  
3 – Up Counter  
4 – Down Counter  
5 – Up / Down Counter  
0 – 31 (Dim – Bright)  
1 - Every Rising Edge  
2 – Every Falling Edge  
3 – Falling Edge / 4  
4 – Falling Edge / 16  
1 – Reset Disabled  
2 – Reset on Keypress  
3 – Reset on S2 Low  
4 – Reset on S2 High  
11  
14  
Display Intensity  
20  
1
Input Trigger / Prescaler Setup  
16  
Counter Mode Reset Configuration  
1
Signal Input #1 (S1) Setup  
Display Reference  
Reference RPM  
20  
21  
22  
23  
1 – 9999 (Display Units)  
1 – 9999 (RPM)  
1000  
1000  
10  
Pulses Per Revolution  
Recovery Rate  
1 – 9999 (PPR)  
0 – 1000 (1/2 seconds)  
0 – Disabled  
10  
> 0 – Recovery 1/2 seconds  
0 – 60 (seconds)  
0 – Disabled  
24  
25  
Display Smoothing / Averaging  
Decimal Point Position  
1
0
> 0 – Averaging Seconds  
0 – DP Disabled (XXXX)  
1 – X.XXX  
2 – XX.XX  
3 – XXX.X  
4 – XXXX.  
26  
Auto-Ranging Configuration  
0 – Auto-Ranging Off  
1 – Auto-Range on Overflow  
2 – Auto-Ranging On  
0 – 9999 (counts)  
0
0
27  
30  
31  
32  
33  
34  
35  
36  
37  
Counter Mode Reset / Preload Value  
Reserved  
Reserved  
Reserved  
Reserved  
Reserved  
Reserved  
Reserved  
Counter Gate Configuration  
1 – Disabled  
1
2 – Counting Enabled (Low)  
3 – Counting Enabled (High)  
Download from Www.Somanuals.8com. All Manuals Search And Download.  
Software Parameters, cont'd  
Value Range  
(units)  
Factory  
Settings  
User  
Parameter  
Description  
Alarm Output #1 Configuration  
Activation Conditions  
Settings  
40  
0 – Always Off  
0
1 – Always On  
2 – Active when Above  
3 – Active when Below  
4 – Active inside Range  
5 – Active outside Range  
1 – Constant & Auto Reset  
2 – Constant & Manual Reset  
3 – Pulsed & Auto Reset  
4 – Pulsed & Manual Reset  
1 – No Sil., Reset on Key  
2 – No Sil., Reset on S2 High  
3 – No Sil., Reset on S2 Low  
4 – Sil., Reset on Key  
41  
42  
Output Style & Reset Mode  
Reset Configuration  
1
1
5 – Sil., Reset on S2 High  
6 – Sil., Reset on S2 Low  
0 – Alarm Flash Disabled  
1 – Alarm Flash Enabled  
1 – 3600 (seconds)  
43  
Display Flash On Active Alarm  
0
44  
45  
46  
47  
48  
Pulse on Time  
Pulse off Time  
Pulse Count  
Lower Limit  
1
1
1 – 3600 (seconds)  
0 – 9999 (pulses)  
0
0 – 9999 (display units)  
0 – 9999 (display units)  
0
Upper Limit  
9999  
Alarm Output #2 Configuration  
50  
Activation Conditions  
0 – Always Off  
0
1 – Always On  
2 – Active when Above  
3 – Active when Below  
4 – Active inside Range  
5 – Active outside Range  
1 – Constant & Auto Reset  
2 – Constant & Manual Reset  
3 – Pulsed & Auto Reset  
4 – Pulsed & Manual Reset  
1 – No Sil., Reset on Key  
2 – No Sil., Reset on S2 High  
3 – No Sil., Reset on S2 Low  
4 – Sil., Reset on Key  
5 – Sil., Reset on S2 High  
6 – Sil., Reset on S2 Low  
0 – Alarm Flash Disabled  
1 – Alarm Flash Enabled  
1 – 3600 (seconds)  
51  
52  
Output Style  
1
1
Reset Configuration  
53  
Display Flash On Active Alarm  
0
54  
55  
56  
57  
58  
Pulse On Time  
Pulse Off Time  
Pulse Count  
Lower Limit  
1
1
1 – 3600 (seconds)  
0 – 9999 (pulses)  
0
0 – 9999 (display units)  
0 – 9999 (display units)  
0
Upper Limit  
9999  
Parameter Memory Commands  
95  
98  
99  
Restore to Factory Settings  
0 – Do Nothing & Exit  
5 – Restore Factory Settings  
0 – Do Nothing & Exit  
5 – Save Setting  
0
0
0
Save to User Setting Area  
Restore from User Setting Area  
0 – Do Nothing & Exit  
1 – Restore Settings  
Download from Www.Somanuals.com. 9All Manuals Search And Download.  
Parameter Descriptions  
Parameter 0 – Exit to Running Mode  
Whenparameter0isselectedinParameter-SelectionMode,theunitwillreturntoRunningMode  
and display the running valueꢀ This should be selected once changes to parameters are  
completedꢀ  
Parameter 1 – Model Number (Read Only)  
This is a number which represents the base model number for the productꢀ For the DTM8000,  
the model code is 80ꢀ  
Parameter 2 – Software Build (Read Only)  
The software build is a code which identifies the software version of the unitꢀ  
Parameter 3 – Hardware Version (Read Only)  
The hardware version is a code which identifies which hardware was used to build the unitꢀ  
Parameter 4 & 5 – Serial Number, Major & Minor (Read Only)  
These parameters are reserved for future use as an electronic serial number and are unique to  
each manufactured unitꢀ  
Parameter 10 – Operating Mode  
This parameter defines the basic mode of operation for the entire unitꢀ It determines if the unit  
is measuring rate, time, or count informationꢀ The following modes are available:  
Mode 1 – Rate Mode  
Rate mode displays measurements in rate units such as RPM, Gallons per Hour, or Feet  
per Secondꢀ  
Mode 2 – Time Mode  
Time mode displays measurements in time units using the format AA:BBꢀ By default  
AA:BB represents minutes (AA) and seconds (BB)ꢀ Optionally, it can be configured to  
represent hours(AA)andminutes(BB)orotheruser-definedunitswitha1:60relationshipꢀ  
Mode 3 – Up Counter  
Counter modes (3 – 5), display measurements in pulse counts or user-defined units which  
are proportional to pulse countꢀ In these modes, the DTM8000 will count the pulses which  
are applied to the S1 input and display the related valueꢀ In this mode, each input pulse  
increments the counterꢀ  
Mode 4 – Down Counter  
Same as Mode 3 above except each input pulse decrements the counterꢀ  
Mode 5 – Up / Down Counter  
Same as Mode 3 above except each input pulse either increments or decrements the  
counter depending upon the state of Signal Input #2 (S2)ꢀ If S2 is tied to common, the  
counter is incremented; otherwise, it is decrementedꢀ  
Parameter 11 – Display Intensity  
This parameter adjusts the intensity of the LED display digits in the front panel of the unitꢀ The  
values of 0 – 31 correspond to a gradual change from very dim to very brightꢀ This is often useful  
when used in the same panel as other pieces of equipment with LED displays and a uniform  
display brightness is desiredꢀ  
Parameter 14 – Input Triggers / Prescale  
This parameter determines how the S1 signal input is processedꢀ It specifies which signal edge  
is used for the measurements and the value of the internal frequency divider or prescalerꢀ  
Modes 3 and 4 should only be used if the input pulse rate exceeds the unit's maximum native  
pulse rate (see specifications for details); otherwise, timing and counting calculations may  
become sluggish and unnecessarily inaccurateꢀ  
Mode 1: Every Rising Edge, No Prescaler  
In this mode, the signal input is measured at every rising edgeꢀ  
Mode 2: Every Falling Edge, No Prescaler  
In this mode, the signal input is measured at every falling edgeꢀ  
10  
 
Mode 3: Falling Edge, Prescaler = 4  
Inthismode,thesignalinputismeasuredatevery4thfallingedgeꢀ Thismodeisespecially  
useful when the signal input frequency is beyond the native pulse-per-minute range of the  
DTM8000ꢀ Because unit will automatically compensates for the prescaler, there is no  
need to factor in the prescaler value when setting the Display and RPM Reference  
parametersꢀ  
Mode 4: Falling Edge, Prescaler = 16  
Same as Mode 3 except the signal input is only measures every 16th falling edgeꢀ  
Parameter 16 – Counter Reset Configuration  
In counter applications, it is often desirable to have the user or an external signal reset the  
counter value to zero or some predetermined valueꢀ This parameter specifies which actions  
will cause the counter to reset to the Counter Reset / Preset Value, parameter 27ꢀ  
Mode 1: Reset Disabled  
The counter cannot be resetꢀ  
Mode 2: Reset On Button Press  
The counter will reset to the Counter Reset / Preset Value, parameter 27, when any of the  
user-interface buttons are depressedꢀ  
Mode 3: Reset On S2 Input Low (Wired To Common)  
The counter will reset to the Counter Reset / Preset Value, parameter 27, when S2 (signal  
2) is brought to an electrically low state or wired to the unit's commonꢀ  
Mode 4: Reset On S2 Input High (Not Wired To Common)  
The counter will reset to the Counter Reset / Preset Value, parameter 27, when S2 (signal  
2) is brought to an electrically high state (+5V) or left to float disconnected from the unit's  
commonꢀ  
Parameter 20 – Signal Input 1 (S1) Display Reference  
This is the number to be displayed when at the user-specified motor Reference RPMꢀ In Rate  
Mode, this value represents the numerator of the rate unit such as feet, ounces, or revolutionsꢀ  
In Time Mode, this value represents the reference time measured in seconds or minutesꢀ If the  
desireddisplayisHH:MM,thenallvaluesshouldbeenteredinminutesꢀ IfMM:SSisdesired,then  
all values should be entered in secondsꢀ In Counter Modes, this value is the reference count  
ratio which corresponds to the number of counts which equate to the specified number of  
reference pulses, parameter 21ꢀ See applications for examplesꢀ  
Parameter 21 – Signal Input 1 (S1) Reference RPM (Reference Pulses in Counter Modes)  
This is the reference RPM at which the Display Reference value should be displayedꢀ In Rate  
and Time Modes, this value represents the RPM of the encoder to which the Display Reference  
correspondsꢀ In Counter Modes, this value is the Reference Pulses which correspond the the  
specified number of displayed counter, parameter 21ꢀ See applications for examplesꢀ  
Parameter 22 – Signal Input 1 (S1) Pulses per Revolution  
This is the number of pulses per revolutionꢀ Value may be from 1 to 9999ꢀ  
Parameter 23 – Signal Input 1 (S1) Recovery Rate  
This is the rate at which the display will attempt to recover once the pulse train appears to have  
stoppedꢀ The recovery rate is the number of half seconds which the unit will wait before dividing  
(Rate Mode) or multiplying (Time Mode) the display value by 2 in an attempt to accurately  
represent the current speed or timeꢀ In the absence of input pulses, this will continue at regular  
intervals until either 0 (Rate Mode) or 99:99 (Time Mode) is reachedꢀ Setting this parameter to  
0 will disable the automatic recovery featureꢀ If this parameter is set too low for the application,  
thedivisionormultiplicationmayprematurelyoccurcausingthereadingtoreadtoohigh,toolow,  
or unstableꢀ This can easily be corrected by simply increasing this parameter's value or  
disabling it by setting it to zeroꢀ  
Parameter 24 – Signal Input 1 (S1) Display Smoothing / Averaging  
This is the amount of time, in 1-second increments, which will be averaged before updating the  
displayꢀ Setting this parameter to 0 will disable the averaging featureꢀ  
11  
 
Parameter 25 – Signal Input 1 (S1) Decimal Point (DP) Position  
Thisselectstheformatofthedisplaywithrespecttothedecimalpoint’spositionꢀ Thisparameter  
does not effect the value entry for other parametersꢀ For example, it the user desires to display  
10ꢀ00 at an input of 300RPM, then parameter 20 would be set to 1000, parameter 21 would be  
set to 300, and parameter 25 would be set to 2ꢀ  
Mode 0: Fixed XXXX  
Mode 1: Fixed XꢀXXX  
Mode 2: Fixed XXꢀXX  
Mode 3: Fixed XXXꢀX  
Mode 4: Fixed XXXXꢀ  
Parameter 26 – Signal Input 1 (S1) Auto-Ranging Configuration  
This selects how the unit auto-ranges and formats the numbers for the displayꢀ  
Mode 0: Auto-Ranging Disabled  
The auto-ranging mode is disabledꢀ Ignoring decimal points, this limits the units display  
range from 0 to 9999ꢀ Values beyond this range will display as an overflow error (-OF-)ꢀ  
Mode 1: Auto-Ranging On Overflow Only  
In this mode, auto-ranging will only be activated if the display value exceeds the maximum  
native display valueꢀ For example, in XXꢀXX decimal point mode, 99ꢀ99 would be the  
maximum native value for a 4-digit displayꢀ When the display is in overflow, it will display  
only the 4 most significant digits and the decimal point will flashꢀ  
Mode 2: Auto-Ranging Always Active  
Inthismode,auto-rangingisalwaysactiveandcontinuouslyattemptstodisplaythe4most  
significant digitsꢀ For example, the display will automatically range from 0ꢀ001 to 9999 as  
neededꢀ In this mode, any value over 9999 will be displayed as an overflow error (-OF-)ꢀ  
Parameter 27 – Counter Reset / Preset Value  
Thisisthevaluethatwillautomaticallybeloadedintothedisplayafterthecounterhasbeenresetꢀ  
See Counter Reset Configuration, parameter 16, for more detailsꢀ  
Parameter 30, 31, 32, 33, 34, 35, and 36  
Reserved For Future Useꢀ  
Parameter 37 – Signal Input 2 (S2) Counter Gate (Enable / Disable) Configuration  
This selects how the S2 input is utilized in single channel counter modesꢀ  
Mode 1: Disabled (Required For Up / Down Counter Mode)  
The S2 input will not function as a gate control and instead will act as the second input for  
dual-channel counter operationꢀ  
Mode 2: Counting Enabled When S2 Input Low (Wired To Common)  
The unit will continue to count input pulses as long as the S2 is in an electrically low state  
or connected to the unit's common terminalꢀ When the S2 input goes high (+5V) or is  
allowed to float disconnected, the counter will be frozen at its current valueꢀ  
Mode 3: Counting Enabled When S2 Input High (Not Wired To Common)  
The unit will continue to count input pulses as long as the S2 is in an electrically high (+5V)  
state or allowed to float disconnectedꢀ When the S2 input goes low or is wired to the unit's  
common, the counter will be frozen at its current valueꢀ  
Parameter 40 & 50 – Alarm 1 & 2 Conditions  
This defines which conditions will result in the alarm 1 or alarm 2 outputs being activatedꢀ  
Mode 0: Always Inactive  
The alarm output will remain in an inactive stateꢀ In this state, the NC and C contacts will  
be internally electrically connectedꢀ  
Mode 1: Always Active (When Power Is Applied)  
The alarm output will become active when the power is applied to the unitꢀ In this state,  
the NO and C contacts will be internally electrically connectedꢀ  
Mode 2: Active When Display Value Above Limit  
The alarm output will activate when the displayed value is above the upper limit settings,  
parameters 48 and 58 accordinglyꢀ  
12  
 
Mode 3: Active When Display Value Below Limit  
The alarm output will activate when the displayed value is below the lower limit settings,  
parameters 47 and 57 accordinglyꢀ  
Mode 4: Active When Display Value Inside Range  
The alarm output will activate when the displayed value is greater than or equal to lower  
limit settings and less than or equal to the upper limit settingꢀ  
Mode 5: Active When Display Value Outside Range  
The alarm output will activate when the displayed value is less than the lower limit setting  
or greater than upper limit settingꢀ  
Parameter 41 & 51 – Alarm 1 & 2 Output Style & Reset Configuration  
This setting configures the output mode and reset method for the alarm outputsꢀ  
Mode 1: Constant & Auto Reset  
In this mode, the alarm output will remain active until the alarm condition ceases to existꢀ  
The alarm will automatically reset when the conditions return to normalꢀ  
Mode 2: Constant & Manual Reset  
In this mode, the alarm output will remain active until the alarm is reset manuallyꢀ See  
parameters 42 and 52 for detailsꢀ  
Mode 3: Pulse & Auto Reset  
Inthismode, thealarmoutputwillpulseonandoffuntilthealarmconditionceasestoexistꢀ  
The pulsed modes are commonly used for audible alarms where a constant output would  
be considered distracting or awkwardꢀ The alarm will automatically reset when the  
conditions return to normalꢀ  
Mode 4: Pulse & Manual Reset  
In this mode, the alarm output will pulse on and off until the alarm is reset manuallyꢀ See  
parameters 42 and 52 for reset detailsꢀ The pulsed modes are commonly used for audible  
alarms where a constant output would be considered distracting or awkwardꢀ  
Parameter 42 & 52 – Alarm 1 & 2 Reset Configuration  
This setting determines which actions will cause an active alarm to be silenced or resetꢀ  
Mode 1: No Silencing, Reset On Any Button Press  
In this mode, an active alarm cannot be silencedꢀ Once the alarm condition ceases to  
exist, however, any user-interface button may be pressed to cause a manual resetꢀ  
Mode 2: No Silencing, Reset On S2 Input High (Not Wired To Common)  
Similar to Mode 1ꢀ Once the alarm condition ceases to exist, setting the S2 input to a high  
(+5V) state or allowing it to float disconnected will cause a manual resetꢀ  
Mode 3: No Silencing, Reset On S2 Input Low (Wired To Common)  
Similar to Mode 1ꢀ Once the alarm condition ceases to exist, setting the S2 input to a low  
(COM) state or wiring it to common will cause a manual resetꢀ  
Mode 4: Silencing Enabled, Reset On Any Button Press  
When the conditions for an active alarm persist, pressing any user-interface button will  
result in the alarm being silenced or deactivated, but not resetꢀ A second attempt to reset  
the alarm must be made after the condition cease to exist to clear the alarmꢀ  
Mode 5: Silencing Enabled, Reset On S2 Input High (Not Wired To Common)  
Similar to Mode 4ꢀ Setting the S2 input to a high (+5V) state or allowing it to float  
disconnected will cause the alarm to be silenced or reset depending on the current state  
of the alarm conditionsꢀ  
Mode 6: Silencing Enabled, Reset On S2 Input Low (Wired To Common)  
Similar to Mode 4ꢀ Setting the S2 input to a low (COM) state or wiring it to common will  
cause the alarm to be silenced or reset depending on the current state of the alarm  
conditionsꢀ  
Parameter 43 & 53 – Alarm 1 & 2 Display Flash On Alarm  
This will cause the display to flash when an alarm conduction is activeꢀ  
Parameter 44 & 54 – Alarm 1 & 2 Pulse on Time  
This parameter defines the number of seconds the output should be enabled during the ‘on’  
phase of an active pulsing alarm’s outputꢀ See application samples for examplesꢀ  
13  
 
Parameter 45 & 55 – Alarm 1 & 2 Pulse off Time  
This parameter defines the number of seconds the output should be disabled during the ‘off’  
phase of an active pulsing alarm’s outputꢀ  
Parameter 46 & 56 – Alarm 1 & 2 Pulse Count  
This setting determines how many pulses are output when the alarm is activated and is  
configuredinpulseoutputstyleWhen0isentered,theunitwillbesetforcontinuouspulseswhile  
the alarm is activeꢀ  
Parameter 47 & 57 – Alarm 1 & 2 Lower Limit  
Thissettingdefineseitherthelowerlimitorlowerendofarangeforthealarmregionꢀ Alarmlimits  
are set in display units without regard to decimal point or colon positionꢀ In Rate and Counter  
Modes, a limit of 123 could represent a display value of 123, 12ꢀ3, 1ꢀ23, or 0ꢀ123ꢀ When in Time  
Mode, a limit of 123 would represent 1:23 on the displayꢀ  
Parameter 48 & 58 – Alarm 1 & 2 Upper Limit  
This setting defines either the upper limit or upper end of a range for the alarm regionꢀ Alarm  
limits are set in display units without regard to decimal point or colon positionꢀ In Rate and  
CounterModes, alimitof123couldrepresentadisplayvalueof123, 12ꢀ3, 1ꢀ23, or0ꢀ123ꢀ When  
in Time Mode, a limit of 123 would represent 1:23 on the displayꢀ  
Parameter 95 – Factory Settings Command  
When set to a value of 5, the unit will be reset to factory settingsꢀ This can also be achieved by  
applying power to the unit with both the Enter and Down buttons depressedꢀ The programming  
jumper must be in the "On" position for this method to functionꢀ  
Parameter 98 – Save to User Settings Area Command  
When set to a value of 5, the unit will store all adjustable parameters to the user settings areaꢀ  
The user settings area is intended to be a location where a user can store settings specific to  
their applicationꢀ A user can easily refresh their custom settingsꢀ Another common use for this  
area is testing and initial setupꢀ The user can store known-good settings here and easily  
experiment without the fear of losing the optimal configurationꢀ  
Parameter 99 – Restore from User Settings Area Command  
Whensettoavalueof1, theunitwillrestorethealladjustableparametersfromtheusersettings  
areaꢀ See parameter 98 for additional informationꢀ  
14  
 
Application Examples  
Pump Flow Monitor with Audible and Visual Alarm  
Description:  
A pump monitor which displays the pump rate in gallons per minute with an audible and visual  
alarm output which will warn the operator of excessively low flow conditions under 5ꢀ00 GPMꢀ  
The alarm should not be able to be silenced and should be reset when any front-panel button is  
pressedꢀ The display should indicate in the format “xxꢀxx” (GPM)ꢀ Due to normal fluctuations in  
flow rates, it is desirable to have the display filter or average the value over 3 seconds to produce  
a more accurate and steady displayꢀ  
Application Diagram:  
Motor Control  
Fluid  
Outlet  
Encoder  
Fluid  
Inlet  
Pump  
ENTER  
36.24  
TACHOMETER  
Pump Specs:  
53 Shaft Rotations = 3 Gallons  
DTM8000 Meter  
Audible  
Annunciator  
Wiring Diagram:  
NC2  
C2  
Not Used  
Not Used  
Not Used  
P1-1  
P1-2  
P1-3  
P1-4  
P1-5  
P1-6  
P1-7  
P1-8  
NO2  
NC1  
C1  
120VAC  
Audible  
Not Used  
Annunciator  
NO1  
N
DTM8000-6  
2 Amp  
AC Line Input 85-265VAC, 50-60 Hz  
L
}
COM  
+5V  
black  
P1-9  
red  
P1-10  
P1-11  
P1-12  
S1  
S2  
white  
Not Used  
Encoder  
Parameter Configuration:  
Parameter  
Value  
Notes  
Rate Mode Setting (GPM is a rate-based unit)  
10  
20  
21  
22  
24  
25  
40  
41  
42  
43  
47  
1
300  
53  
10  
3
Display should indicate 3.00 GPM (300) when motor at Reference RPM, parameter 21  
This is the RPM at which the Display Reference, parameter 20, should be displayed  
Pulses per revolution of shaft encoder or pickup is 10 PPR  
Display filtering / averaging set to 3 seconds  
2
Decimal point position set to XX.XX on display  
3
Alarm active when display value is below lower limit  
Constant alarm output with manual reset required  
2
1
No silencing, reset on any button press  
1
Flash display when alarm is active  
500  
Lower limit setting for 5.00 GPM (500). Limits are entered without regard for decimal  
point position  
15  
 
Conveyor Oven Time Monitor with Over-Heating Alarm  
Description:  
Anovenmonitordisplayingthetunneltimeinminutesandsecondsꢀ Thetunneltimeisdefined  
as the time it takes for the heated object on the conveyor to travel from point A to point B in the  
application diagram belowꢀ A visual indicator should activate if the tunnel time rises above a  
preset limit of 22 minutes and 30 seconds which could cause overheating of the processed  
materialꢀ The indicator should automatically reset when the tunnel time returns to the normal  
operating rangeꢀ For ease of use, the display should be averaged over a period of 1 secondꢀ  
Application Diagram:  
Motor Control  
Connect to  
Coupling  
A
B
Heat Source  
Tunnel Oven  
Coupling to  
Chain Drive  
Encoder  
Gear Motor  
ENTER  
18:40  
TACHOMETER  
Drive Train Specs:  
1250 RPM at non-reduced  
motor shaft equates to  
9 minutes and 15 seconds  
of tunnel time  
DTM8000 Meter  
Wiring Diagram:  
NC2  
C2  
Not Used  
P1-1  
P1-2  
P1-3  
P1-4  
P1-5  
P1-6  
P1-7  
P1-8  
Not Used  
Not Used  
NO2  
NC1  
C1  
Not Used  
Not Used  
Not Used  
NO1  
N
DTM8000-6  
2 Amp  
AC Line Input 85-265VAC, 50-60 Hz  
L
}
COM  
+5V  
black  
P1-9  
red  
P1-10  
P1-11  
P1-12  
S1  
S2  
white  
Encoder  
Parameter Configuration:  
Parameter  
Value  
2
Notes  
10  
20  
Time Mode Setting  
555  
Display should indicate 9:15 (555) when motor at Reference RPM, parameter 21. In  
time mode, all display values are entered in total number of seconds.  
For example, 555 = (9 minutes * 60 seconds-per-minute) + 15 seconds.  
This is the RPM at which the Display Reference, parameter 20, should be displayed.  
Pulses per revolution of shaft encoder or pickup is 10 PPM  
Display filtering / averaging set to 1 seconds  
21  
22  
24  
40  
41  
43  
48  
1250  
10  
1
4
Alarm active when display value is above upper limit  
Constant alarm output with automatic reset  
1
1
Flash display when alarm output is active  
1350  
Upper limit setting for 22 minutes and 30 seconds. In time mode, all limits are entered in  
total number of seconds.  
For example, 1350 = (22 minutes * 60 seconds-per-minute) + 30 seconds.  
16  
 
Take-up / Pay-out Reel Material Measurement with Alarm  
Description:  
A take-up / pay-out system where the DTM8000 displays a measurement of dispensed or  
accumulated material in linear yardsꢀ Once the desired amount of material, 1500 yards,  
hasbeendispensedoraccumulated, anexternallightshouldilluminatetoindicatethatthe  
specifiedmaterialvolumehaspassedꢀ Atthispoint,theusermustbeabletopressabutton  
on the user interface to reset the count to zero and the process repeatsꢀ  
Application Diagram:  
Capstan Drive Specs:  
Capstan  
Motor  
28.3 Revolutions of the  
Capstan motor equate to  
50 linear yards of material  
Belt  
Speed Control  
Pinch Rollers  
Tension  
Belt  
Tension  
Motor #1  
Belt  
Motor #2  
Encoder  
Tension  
Tension  
Torque  
Control #2  
Torque  
Control #1  
I
ENTER  
3650  
TACHOMETER  
Pylon-Style  
Illuminated  
Alarm  
DTM8000 Meter  
Wiring Diagram:  
120VAC  
Illuminated  
Pylon-Style  
Alarm  
NC2  
Not Used  
Not Used  
Not Used  
P1-1  
C2  
P1-2  
P1-3  
P1-4  
P1-5  
P1-6  
P1-7  
P1-8  
NO2  
NC1  
C1  
Not Used  
NO1  
N
DTM8000-6  
2 Amp  
AC Line Input 85-265VAC, 50-60 Hz  
L
}
COM  
+5V  
black  
P1-9  
red  
P1-10  
P1-11  
P1-12  
S1  
S2  
white  
Not Used  
Encoder  
Attached to Driven  
Capstan Pinch Rollers.  
Parameter Configuration:  
Parameter  
Value  
Notes  
10  
16  
20  
3
2
Up-Counter Mode Setting  
Configure counter to reset on any button press  
500  
Display should increment 50 linear yards for each Reference Count, parameter 21.  
Because the initial values were 28.3 revolutions per 50 linear yards, each is multiplied by  
10 to give an even number to increase accuracy since the display can be programmed in  
whole numbers.  
21  
283  
In count mode, the Reference RPM is set in revolutions. 283 has been entered here to  
represent 28.3 revolutions and the Display Reference has also been multiplied by 10 to  
yield whole numbers.  
22  
40  
41  
42  
48  
10  
4
Pulses per revolution of shaft encoder or pickup is 10 PPM  
Alarm active when display value is above upper limit  
Constant alarm output with manual reset required  
No silencing, reset on any button press  
2
1
1500  
Upper limit setting for 1500 linear yards  
17  
 
Bi-directionalIncrementalPositionDisplay  
Description:  
A system is needed which will track the position of a bi-directional linear-motion platform  
and allow the user to select a home or zero positionꢀ The display should read in inches  
and indicate the position of the platform at all timesꢀ  
Application Diagram:  
Platform  
Drive Train Specs:  
40 Revolutions = 3.5 In.  
of Platform Motion  
Connect to  
Coupling  
Linear-Motion System  
Coupling to  
Chain Drive  
Encoder  
Gear Motor  
ENTER  
263.4  
TACHOMETER  
DTM8000 Meter  
Motor Control  
Wiring Diagram:  
NC2  
C2  
Not Used  
Not Used  
Not Used  
P1-1  
P1-2  
P1-3  
P1-4  
P1-5  
P1-6  
P1-7  
P1-8  
NO2  
NC1  
C1  
Not Used  
Not Used  
Not Used  
NO1  
N
DTM8000-6  
2 Amp  
AC Line Input 85-265VAC, 50-60 Hz  
L
}
COM  
+5V  
black  
P1-9  
red  
P1-10  
P1-11  
P1-12  
S1  
S2  
white  
brown  
Encoder  
Parameter Configuration:  
Parameter  
Value  
5
Notes  
10  
20  
Up/Down Counter Mode  
35  
Because the initial values were 40 revolutions per 3.5 inches of platform motion, each is  
multiplied by 10 to give an even number to increase accuracy since the display can be  
programmed in whole numbers. Additionally, because of the decimal point position, the  
Display Reference is multiplied by 10 to generate the proper display format. Without the  
second multiplication by 10, the display would only read 3.5 inches when the drive motor  
turned 400 revolutions.  
21  
400  
In count mode, the Reference RPM is set in revolutions. 400 has been entered here to  
represent 40 revolutions and the Display Reference has also been multiplied by 10 to yield  
whole numbers.  
22  
25  
10  
3
Pulses per revolution of shaft encoder or pickup is 10 PPM  
Decimal point position set to XXX.X on display  
18  
 
Troubleshooting  
Problem  
Possible Case  
Solution  
Display is blank  
Power not applied  
Using a volt meter, verify that a voltage between 85 and 265VAC is measured between  
the L and N terminal block positions.  
Contact technical support for additional help and instructions.  
Defective unit  
Display is dim  
Display intensity  
parameter is too low  
Editing and increasing the display intensity parameter should cause the display digits to  
become brighter.  
When power is  
applied, “LF-L” is  
displayed  
AC line supplying  
power to unit has too  
much noise  
Review routing of power wires in machine to minimize electrical noise. Look for other  
devices which share the same circuit which may be producing unacceptable levels of line  
noise. In some applications, such as welding equipment, a careful regiment of applying  
an AC line filter, re-routine wires, dividing circuits, using shielded cable, and properly  
grounding devices will usually solve the problem.  
AC line supplying  
power to unit has an  
abnormally low  
frequency  
The unit is designed to operate with AC lines from 48-62 Hertz (cycles per second).  
When power is  
applied, “LF-H” is  
displayed  
AC line supplying  
power to unit has too  
much noise  
Review routing of power wires in machine to minimize electrical noise. Look for other  
devices which share the same circuit which may be producing unacceptable levels of line  
noise. In some applications, such as welding equipment, a careful regiment of applying  
an AC line filter, re-routine wires, dividing circuits, using shielded cable, and properly  
grounding devices will usually solve the problem.  
AC line supplying  
power to unit has an  
abnormally high  
frequency  
The unit is designed to operate with AC lines from 48-62 Hertz (cycles per second).  
The first or second Second alarm output  
alarm output does parameters not  
Second alarm output parameters not configured properly  
Review alarm output #2 parameters. The first and second alarm relay outputs can be  
tested by selecting the “Always On” value for the Activation Condition parameters for the  
respective alarm output. When doing this, the relay click should be audible and the NC  
(Normally Closed) and C (Common) terminals should become internally shorted at the  
terminal block.  
not seem to  
function  
configured properly  
19  
 
- Notes -  
20  
 
- Notes -  
21  
 

3Com Power Supply 3644A User Manual
Abocom Network Card WG2000 User Manual
Abocom Switch SW800 User Manual
Acer Flat Panel Television AT2621 AT2622 User Manual
Acu Rite Weather Radio 02032C 888143 User Manual
Addonics Technologies Portable Media Storage ST4ESA User Manual
ADTRAN Telephone IP601SIP User Manual
Alpha ToolComHK Limited Sander VSP 230 User Manual
Audiovox Remote Starter APS 685 User Manual
Beckett Water Gardening Outdoor Fountain LT20 User Manual